Pylontech Battery - Basic Troubleshooting Guide (Batteries not discharging - Battery Monitor [512] Internal Failure Alarm)

Pylontech Battery - Basic Troubleshooting Guide (Batteries not discharging - Battery Monitor [512] Internal Failure Alarm)

Once this is reported by the customer, we must first request for photos of the whole setup to check any wiring/connection anomalies. Then confirm the number of affected batteries by following the steps below

1:
On the VRM portal, Go to Remote Console 


Step 2: Check how many batteries are actually being detected VS. how many batteries there are on site by clicking on Devices, then Pylontech battery



Step 3: Scroll down to see no. of online and offline battery modules as well as no. of modules blocking charge/discharge:

Step 4: Once determined that a battery is faulty (usually indicated by a solid RED light on the inverter), it must be isolated from the system.

Step 5: Follow shutdown, wiring, set-up, and start-up procedure from this guide: Setting Up Pylontech US5000 Batteries with a Victron System

It’s important to note that disconnecting a single battery without adjusting the configuration and wiring it appropriately could cause system errors, as the controller may still try to communicate with the missing unit.
    • Related Articles

    • Pylontech Battery – Basic Troubleshooting Guide

      This guide outlines the correct wiring, startup, and shutdown procedures for integrating Pylontech US5000 lithium batteries with a Victron inverter system via CAN-bus communication. It is compatible with Victron and Deye hybrid inverters. Quick Check ...
    • BSL Battery – Basic Troubleshooting Guide

      Use this guide when setting up a BSL battery stack, or if your BSL batteries are connected but not working. Quick Check Verify CAN cable connection The cable from the inverter must be connected to the CAN port of the master battery. Inspect the RS485 ...
    • Understanding Battery Cell Imbalance

      Battery banks configured in parallel are common in solar energy storage systems. While parallel configurations increase amp-hour (Ah) capacity and enable higher energy reserves at a constant voltage, they also introduce a critical challenge: State of ...
    • How to Fix Battery Cell Imbalance (BSL Battery)

      A battery cell imbalance may present through unusual SOC (State of Charge) behavior, red LED indicators, or system instability. If one battery in the stack is out of balance, it can cause inconsistent charging and affect overall performance. The goal ...
    • ⁠Does discharging a BSL battery to 5% affect performance and warranty?

      Discharging a BSL battery down to 5% won’t harm its performance or void the warranty. These batteries are built to handle deep discharges, meaning you can safely use up to 95% of the battery’s total capacity before charging again. This makes BSL ...